Carbon Dioxide Detectors/Controllers

Carbon Dioxide Detectors/Controllers
Product Detailed
Detect CO2 level With or without LCD Modbus RS485 communication Wireless of ZigBee protocol Wall mount or duct mount

CO2 Sensor

Non-Dispersive Infrared Detector (NDIR)

Measurement Range

0~2,000ppm (default)

0~5,000ppm (preset)

Accuracy

±40ppm + 3% of reading @22°C(72°F)

Stability

<2% of full scale over the life of the sensor

Calibration

Self-calibration system

Response Time

<5 minutes for 90% step change at low duct speed

Non-linearity

<1% of full scale @22°C(72°F)

Duct Air Velocity

0~450m/min     

Pressure Dependence

0.135% of reading per mm Hg

Warm up time

2 hours (first time)

2 minutes (operation)

Split CO2 sensor

2 meter cable connection between the senor and the controller

Temperature & Humidity Sensor (optional)

Temperature

Relative Humidity

Sensing element:

Band-gap-senor

Capacitive humidity sensor

Measuring range

-20°C~50°C

5 -100%RH

Accuracy

±0.4°C (25°C)

±3%RH (25°C, 40%-60%RH)

Display resolution

0.1°C

0.1%RH

Stability

±0.1°Cper year

±1%RH per year

General Data

 

Power supply

24VAC/24VDC

100VAC~240VAC

Consumption

1.8 W max. ; 1.0 W avg.

LCD display

Display CO2 measurement

or CO2 + temperature& humidity measurements

LCD backlit color-3 color

Green CO2<1000ppm (optimal air quality)     default

Yellow CO2>1000ppm (moderate air quality)   default

Red CO2>1400ppm (poor air quality)        default

The color switch can be preset in parameters

Dry contact output (optional)

1xdry contact output for CO2

3A rated switch contact

Modbus RS485 Interface (optional)

19200bps, 15KV antistatic protection.

Wireless module (optional)

ZigBee 2.4G short distance wireless communication

Operation conditions

-0°C~50°C(32~122°F); 0~95%RH, non condensing

Storage conditions

-20~70°C(-40~158°F)

Net weight

260g

IP class

IP30

Standard Approval

CE-Approval

1.Special used to real-time detect CO2 level in air ducts.

2.NDIR infrared CO2 sensor inside with Self-Calibration and up to 15 years lifetime

3.High accuracy humidity and temperature detection optional

4.With LCD or without LCD selectable

5.Special 3-color backlit LCD design  

6.Providing one dry contact output with presetting the setpoint

7.Modbus RS485 communication interface optional

8.Wireless of ZigBee protocol optional

9.Smart structure with easier wire connection through the external pipe

10.Wall mounted or duct mounted available

11.Special a 180° rotatable fastness position for the probe can change the direction of air detection.

12.Replaceable filter in the probe and extendable probe length

13.Design the convenient and easier buttons for operation

14.CE-Approval