Related Categories:Gas Analyzers
Installed in HVAC return air ducts. Analog 0-10V or 4~20mA outputs selectable LCD display selectable Duct type

CO2 Sensor

Non-Dispersive Infrared Detector (NDIR)

Measurement Range

02,000ppm or 0~5000ppm

Accuracy

±40ppm + 3% of reading @22(72)

Stability

<2% of full scale over the life of the sensor

Calibration

Self-calibration system

Response Time

<5 minutes for 90% step change at low duct speed

Non-linearity

<1% of full scale @22(72)

Duct Air Velocity

0~450m/min     

Pressure Dependence

0.135% of reading per mm Hg

Temperature Dependence

0.2% of full scale per ºC

Warm up time

24 hours (first time)

10 minutes (operation)

Temperature & Humidity Sensor

Temperature

Relative Humidity

Sensing element:

Band-gap-senor

Capacitive humidity sensor

Measuring range

-20~50

5 -100%RH

Accuracy

±0.4 (25)

±3%RH (25, 40%-60%RH)

Display resolution

0.1

0.1%RH

Stability

±0.1per year

±1%RH per year

General Data

 

Power supply

24VAC/24VDC

Consumption

1.8 W max. ; 0.8 W avg.

LCD display

3-color backlit

Display CO2  measurement

or CO2 + temperature& humidity measurements

Analog output

1x0~10VDC or 4~20mA output for CO2

3x 1x0~10VDC or 4~20mA outputs for CO2+ Temperature +RH

The voltage output or current output can be selectable by jumpers

Modbus RS485 Interface

19200bps, 15KV antistatic protection.

Operation conditions

-0~50(32~122); 0~95%RH, non condensing

Storage conditions

-20~70(-40~158)

Net weight

240g

IP class

IP54

Standard Approval

CE-Approval

1.Duct type CO2 transmitter specially used to real-time detect CO2 level in air ducts.

2.NDIR infrared CO2 sensor inside with Self-Calibration and up to 15 years lifetime

3.Humidity and temperature detection optional

4.Combined temperature and humidity sensor provide the highest accuracy in full range

5.LCD display option can display CO2 measurement and temperature+ RH measurements   

6.3-color backlit LCD indicates the CO2 level more clearing and alarm function

7.Providing one or three 0~10VDC or 4~20mA analog outputs

8.Modbus RS485 communication interface makes usage and test more convenient

9.Smart structure and attractive housing provide you a unique operation feeling

10.Simple and skillful design and installation with a demountable and replaceable filter to provides dust-proof protection

11.Special a 180° rotatable fastness position for the probe can change the direction of air detection.

12.All housing and probe are IP54 class

13.CE-Approval